Inverter Duty Transformer for Solar Power Plant
โ Application
- Used in grid-connected solar PV plants
- Converts inverter output (low voltage AC) to grid level voltage
- Provides isolation + voltage step-up
๐ Solar panels โ DC โ inverter โ AC (LV) โ IDT โ 11kV / 33kV grid
๐ท Technical Configuration
โก Voltage Levels
- LT Side (Inverter side):
- 400V / 415V / 690V (typical)
- Multiple LT windings (1, 2, or 3 inputs)
- HT Side (Grid side):
- 11 kV / 33 kV
โก Winding Configuration
- 1 LT winding โ Single inverter connection
- 2 LT windings โ Dual inverter input
- 3 LT windings (or more) โ Multiple inverter inputs
โก Multi-winding design reduces number of transformers in solar plant
โก Capacity Range
- Typical: 100 kVA to 20 MVA
- Can be customized based on plant MW size
โก Phase
- 3 Phase Transformer (mandatory for solar utility plants)
โก Cooling
- ONAN / ONAF (oil cooled)
๐ท Key Design Features (Solar Duty)
These transformers are NOT standard distribution transformers. They are specially designed for:
- Handling harmonics from inverters
- Frequent load fluctuation (cloud effect)
- High ambient temperature operation
- Continuous duty
โ Built with:
- Low-loss CRGO core
- High insulation strength
- Enhanced thermal design
๐ท Standards Compliance
๐ฎ๐ณ Indian Standards (IS)
- IS 2026 โ Power Transformer standard
- IS 1180 โ Efficiency (if applicable)
- IS 335 โ Transformer oil
๐ International Standards
- IEC 60076 โ Power transformers
- ANSI / IEEE (optional project-specific)
โ Most manufacturers explicitly design IDTs as per IS 2026 & IEC 60076
๐ท Typical Technical Specs (Example)
- Capacity: 2.5 MVA โ 10 MVA
- Voltage Ratio: 0.69 kV / 33 kV
- Vector Group: Dyn11 / YNd11
- Frequency: 50 Hz
- Insulation Class: A / E
- Tap Changer: OLTC / OCTC
- Cooling: ONAN