Instrument transformers

Voltage Transformers up to 33kV

Amrest Electricals Limited manufactures voltage transformers (VT / PT) up to 33kV for accurate metering and reliable protection, in single phase and three phase units. Customized solutions are available as per client specifications.

Up to 33kVSingle and three phaseIndoor and outdoor
Voltage transformer manufactured by Amrest Electricals
Our range

Types of voltage transformers

1

Dry-type resin cast

Indoor type. Epoxy resin encapsulated, non-hygroscopic insulation, naturally air-cooled.

  • Single phase / three phase
  • Voltage class up to 33 kV
  • Customized as per client specification
2

Outdoor oil-cooled

Outdoor type with mineral oil insulation and ONAN cooling.

  • Single phase / three phase
  • Voltage class up to 33 kV
  • Hermetically sealed or conservator type, as per requirement
3

Outdoor resin cast

Outdoor type resin cast voltage transformers, oil-free and low maintenance.

  • Single phase / three phase
  • Voltage class up to 33 kV

View outdoor resin cast VT

Specification

Key features at a glance

ParameterDry-type resin castOutdoor oil-cooled
TypeSingle phase / three phaseSingle phase / three phase
Voltage classUp to 33 kVUp to 33 kV
InsulationEpoxy resin encapsulated (non-hygroscopic)Mineral oil (IS 335 / IEC 60296)
CoolingNaturally air-cooled (dry type)ONAN (oil natural air natural)
Secondary voltage110 V or 110/√3 V110 V or 110/√3 V
Rated burden10 VA to 500 VA at 0.8 PF lagging10 VA to 500 VA at 0.8 PF lagging
Frequency50 / 60 Hz50 / 60 Hz
Accuracy class (metering)0.1, 0.2, 0.5, 1.0, 30.1, 0.2, 0.5, 1.0, 3
Accuracy class (protection)3P, 6P3P, 6P
ConstructionResin castHermetically sealed or conservator type, as per customer requirement

Final ratings, burden and accuracy class are defined as per customer/project requirement.

Use

Metering and protection

  • Metering classes: 0.1, 0.2, 0.5, 1.0 and 3 for energy meters and measuring instruments
  • Protection classes: 3P and 6P for protection relays
Standards reference

Applicable standards

  • IS 3156
  • IEC 60044-2 (now part of the IEC 61869 series)
  • ANSI C57

Applicable standards and test documentation are confirmed in the technical offer for each project.

Get a quotation

What to send us

Share as many of these details as you have, or send your datasheet or BOQ directly.

Primary voltage and ratio
Secondary voltage
Rated burden (VA)
Accuracy class
Single or three phase
Indoor or outdoor type
Quantity
Project location
Delivery timeline
Related products

Explore more