Buyer’s guide

Outdoor 33kV Current Transformer Manufacturer in India

Current transformers in an outdoor 33kV substation face rain, dust, pollution, salt near the coast, strong sun and lightning surges, while delivering accurate signals to meters and relays for decades. AMREST Electricals manufactures outdoor 33kV CTs for substations, switchyards, utilities, industries and renewable energy projects. This guide explains what really matters when you choose one.

33kV / 36kV classOutdoor ratedMetering & protection
33kV single phase double bushing outdoor current transformer by AMREST
The basics

What is an outdoor 33kV current transformer?

A 33kV CT converts high line current into a small, proportional secondary current, usually 1A or 5A, for energy meters, protection relays, ammeters and monitoring systems, while isolating that equipment from the high-voltage line. An outdoor CT does the same job, but its insulation, housing and terminals are designed to work in open air on a switchyard structure, without the protection of a panel or building.

AspectIndoor 33kV CTOutdoor 33kV CT
Where installedInside switchgear panels and metering cubiclesOn structures in switchyards and open substations
EnvironmentClean, dry, protectedRain, dust, pollution, UV, temperature swings
Insulation surfaceStandard epoxy resinWeather-resistant material with sheds for longer creepage
Creepage distanceLower, suited to clean indoor airHigher, chosen by site pollution level
Secondary terminalsOpen terminal block inside panelSealed, weatherproof terminal box with cable gland
HardwareStandard fastenersCorrosion-protected fittings
Our range

Outdoor 33kV CT designs

33kV single phase single bushing current transformer by AMREST

Single Phase Single Bushing CT

Compact construction with a straightforward primary connection, for feeder bays, transformer bays and outdoor 33kV structures.

  • Metering, protection or multi-core
  • Ratio, cores, class and burden per project
  • Terminal and mounting as per drawing
33kV single phase double bushing current transformer by AMREST

Single Phase Double Bushing CT

Both primary terminals brought out through separate bushings, where the structure layout or connection method calls for it.

  • Defined primary terminal layout
  • Insulation and creepage for the site
  • Customised to your datasheet
R

Outdoor Resin Cast CT

Windings cast in outdoor-grade cycloaliphatic epoxy that resists UV and surface tracking. Oil-free, low maintenance and no leak risk. See our MV outdoor resin cast CT range.

O

Oil-Immersed Outdoor CT

Active part in insulating oil inside a sealed tank with a porcelain or composite bushing. A long-established choice for outdoor utility substations.

Selection guide

5 things to specify for an outdoor 33kV CT

1

Insulation level

Highest voltage for equipment is 36kV, with typical withstand of 70kV rms and 170kVp lightning impulse. Mention if the site is above 1,000 m altitude, as a correction is needed.

2

Creepage distance

The surface path from HV terminal to earth. Dust or salt plus moisture makes it conductive, so polluted sites need more creepage (see table below).

3

Metering or protection

Metering cores (0.2S, 0.5S) for billing; protection cores (5P10, 5P20, PS) for relays; multi-core for both in one unit.

4

Short-time current

The CT must withstand full fault current until the breaker trips. Specify kA and duration (1 or 3 seconds) from your fault level.

5

Terminal box & hardware

Moisture in the secondary box is a common failure cause. Ask for a sealed box, proper cable gland and corrosion-protected fittings.

+

Construction

Resin cast or oil-immersed, single or double bushing, as per your structure layout and utility specification.

Creepage guide

Creepage distance by site pollution

Site pollutionTypical exampleSpecific creepageApprox. total for 36kV
LightRural areas, low industry16 mm/kV~580 mm
MediumTowns, moderate industry20 mm/kV~720 mm
HeavyIndustrial zones, near coast25 mm/kV~900 mm
Very heavyCoastal, cement, chemical, desert dust31 mm/kV~1,116 mm

Many Indian utilities specify 25 or 31 mm/kV as standard. Always follow your tender or utility specification, and tell us if the site is coastal or near a cement, steel or chemical plant.

At a glance

Typical technical specifications

ParameterTypical requirement
Product typeOutdoor Current Transformer
System voltage33kV (highest system voltage 36kV)
Insulation level70kV rms / 170kVp
ApplicationMetering / Protection / Multi-core
Frequency50 Hz or project requirement
Primary current / CT ratioProject specific
Secondary current1A or 5A
Accuracy classMetering: 0.2S, 0.5S | Protection: 5P10, 5P20, PS
Number of coresSingle / Multiple
Rated burdenAs required
Creepage distanceAs per site pollution level
MountingProject specific

Final specifications are selected according to the applicable standard, system design, site conditions and project requirements.

Installation & safety

Get the site work right

  • Never open-circuit a CT secondary while the line is live. Short it before disconnecting any meter or relay.
  • Earth the CT body and one point of each secondary circuit.
  • Check P1/P2 polarity; reversed polarity causes wrong metering and relay mal-operation.
  • Clean insulator surfaces periodically at polluted sites, especially before the monsoon.
Why AMREST

Built for outdoor duty

  • Single and double bushing 33kV designs
  • Metering, protection and multi-core configurations
  • Specification-first: your datasheet reviewed before manufacturing
  • EPC support: datasheet-based offers and bulk supply
  • Domestic and export supply
Applications

Where they are used

  • 33kV substations
  • Outdoor switchyards
  • Utility installations
  • Industrial substations
  • Solar power plants
  • Wind power projects
  • Outdoor CT PT metering units
  • Power generation facilities
  • Railway and infrastructure projects
Get a quotation

What to send us

Share as many of these details as you have, or send your datasheet or BOQ directly.

CT ratioe.g. 400/1A or 200-400/1A
Number of corese.g. 1 metering + 1 protection
Accuracy class per coree.g. 0.5S and 5P20
Burden per coreVA for each core
Short-time currentkA and duration
Creepage / pollutionmm/kV or site category
ConstructionResin cast or oil; single or double bushing
Site detailsAltitude, coastal or industrial
Quantity & specificationUnits and utility / tender spec
Supply

Manufacturer, exporter and supplier

We supply outdoor 33kV current transformers for India and for projects in the following countries and regions:

  • India
  • United Arab Emirates
  • Saudi Arabia
  • Bahrain
  • Iraq
  • Kuwait
  • Oman
  • Qatar
  • South Africa
  • Zambia
  • Tanzania
  • Ghana
  • Nepal
  • Bhutan
  • Bangladesh
  • Indonesia
  • Kenya
  • Malaysia
  • Turkey
  • Zimbabwe
  • and other countries
FAQ

Frequently asked questions

What is an outdoor 33kV current transformer?

A CT designed for open-air installation on 33kV systems, with weather-resistant insulation, adequate creepage and sealed terminals, that converts high line current into a small secondary current for meters and relays.

Can an indoor CT be used outdoors?

No. Indoor resin and terminals are not designed for UV, rain and pollution. Using an indoor CT outdoors risks surface tracking, moisture ingress and early failure.

What creepage distance is needed for a 33kV outdoor CT?

It depends on site pollution. Heavy pollution typically needs about 25 mm/kV (around 900 mm for 36kV equipment), and very heavy or coastal sites about 31 mm/kV. Follow your utility or tender specification.

Can one outdoor CT handle both metering and protection?

Yes, with a multi-core design that has separate metering and protection cores in one body.

Does AMREST make customised outdoor 33kV CTs?

Yes. Ratio, cores, accuracy class, burden, creepage, terminals and mounting are built to your project specification.